轻钢与EPS混凝土的黏结滑移性能试验研究
作者:
作者单位:

作者简介:

通讯作者:

中图分类号:

基金项目:

国家发改委建筑行业低碳技术创新及产业化示范工程项目(20131819)


Experimental Research on Bond Slip Behavior between Light Gauge Steel and EPS Concrete
Author:
Affiliation:

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    为研究轻钢与聚苯颗粒(EPS)混凝土界面黏结滑移的作用机理,制作了20个轻钢EPS混凝土短柱试件进行拉拔试验,研究EPS混凝土强度、钢管埋置长度及保护层厚度对轻钢与EPS混凝土黏结性能的影响.结果表明:轻钢与EPS混凝土的黏结应力要比钢筋与普通混凝土的黏结应力小;峰值黏结应力随EPS混凝土强度和保护层厚度的增加有所提高;钢管埋置长度的变化对峰值黏结应力的影响不明显.基于试验结果,提出了轻钢与EPS混凝土的三段式黏结滑移本构模型,计算值与试验值基本吻合.

    Abstract:

    According to the pull out tests of 20 specimens, the bond slip mechanism between light gauge steel and expanded polystyrene(EPS) concrete was investigated. The effects of cover thickness, concrete strength and bonded length were studied. Results show that compared with normal reinforced concrete, bond strength between light gauge steel and EPS concrete is lower. Ultimate bond strength is improved with the increase of cover thickness and concrete strength, while bonded length shows little effect on the bond strength. Based on the test results, a three stage bond slip model is proposed to represent the bond behavior of light gauge steel in EPS concrete, which agrees well with the test results.

    参考文献
    相似文献
    引证文献
引用本文

崔成臣,黄强,李东彬,李红超.轻钢与EPS混凝土的黏结滑移性能试验研究[J].建筑材料学报,2016,19(3):578-583

复制
分享
文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:2015-03-05
  • 最后修改日期:2015-04-13
  • 录用日期:
  • 在线发布日期: 2016-06-22
  • 出版日期:
文章二维码